Learning path

Knowledge Hub

From lightning concepts to low-voltage power-line SPD products—a structured guide for engineers, panel builders, and local partners.

12. Multi-Stage SPD Coordination · Page 2 of 5

Distance Between SPD Stages

Cable length as intentional decoupling.

Cable length between SPD stages

Rule of thumb

Many coordination schemes assume a minimum cable length between stages (often on the order of several meters) unless a dedicated decoupler is used.

Short feeder problem

When SDB is only a meter from MDB, verify coordination explicitly—do not assume datasheet Up values alone guarantee staging.

Designers' note

Show both SPD locations and approximate feeder lengths on the single-line diagram.